10~180kVA Modular UPS

$26,000.00

Green theme​ matching the original (dark green section bars + green headers)
Two sub-series grouping: MOD10E (left 3 cols) vs MOD20E (right 3 cols) clearly separated
Added Unit​ and Remarks​ columns — units extracted from values, notes added for clarity
Key numbers highlighted: 97% efficiency, 7″ LCD, 20~120kVA, IP20, ±120/±240VDC
Frozen panes​ (C4) — model header & param column stay visible while scrolling
6 Notes​ at bottom documenting corrections & assumptions (e.g., OCR “4 15” → corrected to 415VAC)

AC Modular UPS Specification (MOD10E / MOD20E Series)
MOD10E Series MOD20E Series
Model AC020/10E AC040/10E AC060/10E AC040/20E AC080/20E AC120/20E Unit Remarks
Main Input
Rated Power 20kVA 40kVA 60kVA 40kVA 80kVA 120kVA kVA Apparent power
Input 3P5W (3P+N+PE) 3P5W (3P+N+PE) 3P5W (3P+N+PE) 3P5W (3P+N+PE) 3P5W (3P+N+PE) 3P5W (3P+N+PE) – Three-phase five-wire
Rated Voltage 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) VAC Line-to-line
Rated Frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz Hz Auto-sensing
Input PF >0.99 >0.99 >0.99 >0.99 >0.99 >0.99 – Full load
Current Distortion (THDi) <2% (100% linear load) <2% (100% linear load) <2% (100% linear load) <2% (100% linear load) <2% (100% linear load) <2% (100% linear load) % IEC 62040
Voltage Range 304~478VAC (full load)
304~228VAC (derate 100%→50%)
304~478VAC (full load)
304~228VAC (derate 100%→50%)
304~478VAC (full load)
304~228VAC (derate 100%→50%)
324~478VAC (full load)
324~228VAC (derate 100%→50%)
324~478VAC (full load)
324~228VAC (derate 100%→50%)
324~478VAC (full load)
324~228VAC (derate 100%→50%)
VAC MOD10E: 10-25kVA; MOD20E: 30kVA (per OCR)
Frequency Range 40~70Hz 40~70Hz 40~70Hz 40~70Hz 40~70Hz 40~70Hz Hz
Battery
Rated Voltage ±120VDC (default 20 pcs,
20-50 pcs selectable)
±120VDC (default 20 pcs,
20-50 pcs selectable)
±120VDC (default 20 pcs,
20-50 pcs selectable)
±240VDC (default 40 pcs,
30-50 pcs selectable)
±240VDC (default 40 pcs,
30-50 pcs selectable)
±240VDC (default 40 pcs,
30-50 pcs selectable)
VDC Number of batteries selectable
Charging Capacity 50%×Pout (limited by input current) 50%×Pout (limited by input current) 50%×Pout (limited by input current) 50%×Pout (limited by input current) 50%×Pout (limited by input current) 50%×Pout (limited by input current) – Charge power
Charging Accuracy ≤1% ≤1% ≤1% ≤1% ≤1% ≤1% –
Bypass
Rated Voltage 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) VAC
Voltage Range -40%~+25%, settable
(default -20%~+15%)
-40%~+25%, settable
(default -20%~+15%)
-40%~+25%, settable
(default -20%~+15%)
-40%~+25%, settable
(default -20%~+15%)
-40%~+25%, settable
(default -20%~+15%)
-40%~+25%, settable
(default -20%~+15%)
%
Overload 110%: long time
110%~125%: 10 min
125%~150%: 1 min
110%: long time
110%~125%: 10 min
125%~150%: 1 min
110%: long time
110%~125%: 10 min
125%~150%: 1 min
110%: long time
110%~125%: 10 min
125%~150%: 1 min
110%: long time
110%~125%: 10 min
125%~150%: 1 min
110%: long time
110%~125%: 10 min
125%~150%: 1 min
– Bypass overload capacity
Inverter (Output)
Rated Voltage 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) 380/400/415VAC (L-L) VAC
Rated Frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz Hz
Output PF 1 1 1 1 1 1 – Unity power factor
Voltage Accuracy ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% %
Output THDu <1% (linear)
<5% (non-linear, IEC 62040-3)
<1% (linear)
<5% (non-linear, IEC 62040-3)
<1% (linear)
<5% (non-linear, IEC 62040-3)
<1% (linear)
<5% (non-linear, IEC 62040-3)
<1% (linear)
<5% (non-linear, IEC 62040-3)
<1% (linear)
<5% (non-linear, IEC 62040-3)
%
Overload 110%: 1 hour
125%: 10 min
150%: 1 min
>150%: 200ms
110%: 1 hour
125%: 10 min
150%: 1 min
>150%: 200ms
110%: 1 hour
125%: 10 min
150%: 1 min
>150%: 200ms
110%: 1 hour
125%: 10 min
150%: 1 min
>150%: 200ms
110%: 1 hour
125%: 10 min
150%: 1 min
>150%: 200ms
110%: 1 hour
125%: 10 min
150%: 1 min
>150%: 200ms
– Inverter overload
Frequency Accuracy ±0.1% ±0.1% ±0.1% ±0.1% ±0.1% ±0.1% %
Synchronize Window Settable 0.5~5Hz (default ±3Hz) Settable 0.5~5Hz (default ±3Hz) Settable 0.5~5Hz (default ±3Hz) Settable 0.5~5Hz (default ±3Hz) Settable 0.5~5Hz (default ±3Hz) Settable 0.5~5Hz (default ±3Hz) Hz
Slew Rate Settable 0.5~3Hz/s (default 0.5Hz/s) Settable 0.5~3Hz/s (default 0.5Hz/s) Settable 0.5~3Hz/s (default 0.5Hz/s) Settable 0.5~3Hz/s (default 0.5Hz/s) Settable 0.5~3Hz/s (default 0.5Hz/s) Settable 0.5~3Hz/s (default 0.5Hz/s) Hz/s
Phase Accuracy 120°±0.5° 120°±0.5° 120°±0.5° 120°±0.5° 120°±0.5° 120°±0.5° °
Efficiency (normal mode) up to 97% up to 97% up to 97% up to 97% up to 97% up to 97% % High efficiency mode
Display & Communication
Display LED + 7″ touch LCD LED + 7″ touch LCD LED + 7″ touch LCD LED + 7″ touch LCD LED + 7″ touch LCD LED + 7″ touch LCD –
Configuration USB, RS232, RS485, Dry contact,
Cold start, Air filter, Ethernet port
USB, RS232, RS485, Dry contact,
Cold start, Air filter, Ethernet port
USB, RS232, RS485, Dry contact,
Cold start, Air filter, Ethernet port
USB, RS232, RS485, Dry contact,
Cold start, Air filter, Ethernet port
USB, RS232, RS485, Dry contact,
Cold start, Air filter, Ethernet port
USB, RS232, RS485, Dry contact,
Cold start, Air filter, Ethernet port
– Standard
Option SNMP card, AS400 card, SPD,
Parallel kit
SNMP card, AS400 card, SPD,
Parallel kit
SNMP card, AS400 card, SPD,
Parallel kit
SNMP card, AS400 card, SPD,
Parallel kit
SNMP card, AS400 card, SPD,
Parallel kit
SNMP card, AS400 card, SPD,
Parallel kit
– Optional accessories
Certification & System
Safety IEC 62040-1, IEC 60950-1 IEC 62040-1, IEC 60950-1 IEC 62040-1, IEC 60950-1 IEC 62040-1, IEC 60950-1 IEC 62040-1, IEC 60950-1 IEC 62040-1, IEC 60950-1 –
EMS IEC 62040-2; IEC 61000-4-2 (ESD);
IEC 61000-4-3 (RS); IEC 61000-4-4 (EFT);
IEC 61000-4-5 (Surge)
IEC 62040-2; IEC 61000-4-2 (ESD);
IEC 61000-4-3 (RS); IEC 61000-4-4 (EFT);
IEC 61000-4-5 (Surge)
IEC 62040-2; IEC 61000-4-2 (ESD);
IEC 61000-4-3 (RS); IEC 61000-4-4 (EFT);
IEC 61000-4-5 (Surge)
IEC 62040-2; IEC 61000-4-2 (ESD);
IEC 61000-4-3 (RS); IEC 61000-4-4 (EFT);
IEC 61000-4-5 (Surge)
IEC 62040-2; IEC 61000-4-2 (ESD);
IEC 61000-4-3 (RS); IEC 61000-4-4 (EFT);
IEC 61000-4-5 (Surge)
IEC 62040-2; IEC 61000-4-2 (ESD);
IEC 61000-4-3 (RS); IEC 61000-4-4 (EFT);
IEC 61000-4-5 (Surge)
–
IP Degree IP20 IP20 IP20 IP20 IP20 IP20 –
Environment
Environment 0~40°C (operation)
-25~70°C (storage)
0~95% RH (non-condensing)
0~40°C (operation)
-25~70°C (storage)
0~95% RH (non-condensing)
0~40°C (operation)
-25~70°C (storage)
0~95% RH (non-condensing)
0~40°C (operation)
-25~70°C (storage)
0~95% RH (non-condensing)
0~40°C (operation)
-25~70°C (storage)
0~95% RH (non-condensing)
0~40°C (operation)
-25~70°C (storage)
0~95% RH (non-condensing)
°C / %
Noise (1m) 65dB @ 100% load
62dB @ 45% load
65dB @ 100% load
62dB @ 45% load
65dB @ 100% load
62dB @ 45% load
65dB @ 100% load
62dB @ 45% load
65dB @ 100% load
62dB @ 45% load
65dB @ 100% load
62dB @ 45% load
dB(A)
Module (Power Module)
Slots 4-Slots (10kVA power module) 4-Slots (10kVA power module) 4-Slots (10kVA power module) 4-Slots (20kVA power module) 4-Slots (20kVA power module) 4-Slots (20kVA power module) –
Dimension (W×D×H) 400×495×86 400×495×86 400×495×86 400×495×86 400×495×86 400×495×86 mm Per module
Weight 13.85 13.85 13.85 13.85 13.85 13.85 kg Per module
Cabinet (Mechanical)
Body Dimension (W×D×H) 442×711×307 (7U) 442×710×485 (11U) 442×661×705 (16U) 442×711×307 (7U) 442×710×485 (11U) 442×661×705 (16U) mm Body only
Max Dimension (W×D×H) 442×751×397 442×751×575 442×841×797 442×751×397 442×751×575 442×841×797 mm With protrusions
Cabinet Weight 39 52 64 39 52 64 kg